Commissioning or operation of the cooling tower is the last step in using the cooling tower in the design of the cooling tower system. Operation is the final step in selecting a cooling tower that has high sensitivities. The correct operation of the cooling tower is in fact the result of the correct selection and installation of the cooling towerAfter completing the installation of the cooling tower, it is necessary to set up the cooling tower and put it into service. The operation of the condenser water system of a heating device such as a chiller or boiler consists of several basic and mandatory parts. In the most important part of designing and operating the condenser system is the cooling tower. The placement and installation of condenser cold water cycle accessories has a significant impact on the output. In fact, the correct operation of the cooling tower is a function of the correct installation of the cooling tower and accessories.

The effect of observing safety issues in setting up a cooling tower !!

Observing the safety points and checking the peripheral equipment in connection with the cooling tower is one of the most important principles of using the cooling tower. In fact, before turning on the cooling tower and starting the condenser system, we must make sure that each equipment is working properly. Proper operation of industrial cooling and air conditioning system has many benefits. Failure to follow the principles in the setup operation may cause damage to the main parts of the devices.

Observing the basic points in the initial start and checking the important items can have a great impact on the basic operation of the cooling tower . The commissioning of an industrial or refrigeration equipment is done correctly when the least amount of error is made in it. Reducing the incidence of errors in the commissioning process by an expert should be done in accordance with the principles of operation of the cooling tower.


Basic principles in setting up a cooling tower

  • How to properly install peripherals such as pumps, cold water tanks, hardeners, etc.

  • Proper arrangement and proper placement of equipment in the condenser cycle

  • Use of protective equipment in the control panel to protect fan and pump motors against human errors

  • Use of cold water flow regulating valves in the piping circuit between the cooling tower and industrial devices

  • Use of shock absorbers in the piping circuit and in the main chassis holding the main equipment

  • Temporary start-up of the system (in the form of a starter) and fixing possible problems

  • Check and re-inspect the checklist by the relevant expert

  • Observe safety tips and setup requirements in accordance with the installation manual provided by the manufacturer

  • Final commissioning of the system and long-term operation of the equipment and elimination of possible defects


The main components to be controlled before starting the cooling tower cooling system

  • cooling tower

  • Cold water storage tank

  • Cool water circulator pump

  • Pipes and fittings (side valves of circulating water circuit)

  • Exothermic device (chiller or industrial device)

  • Circulating water treatment equipment (hardeners or micron filters or RO package)


Control items in the correct installation of the pump in the process of setting up the cooling tower

  • Pump installation control includes mounting the pump, connectors, vibrators and plumbing fixtures such as valves, filters, pressure gauges, thermometers, etc.

  • Axis control (pump shaft and its coupling alignment

  • Lubrication or pump shaft arches according to the manufacturer's instructions

  • Lubrication of motor shaft bearings according to the manufacturer's instructions

  • Rotate the shaft by hand to ensure free rotation of the pump motor

  • Control of the correct direction of rotation of the electric pump shaft with blade starter


Controls in the water treatment system in the cooling tower condenser circuit

  • Control of pH sensor catheters or rods and navigability for proper installation

  • Test the performance of the solenoid valve to drain or adjust the flow of water or underwater

  •  Putting water purification equipment in operation


Final control items before setting up the cooling tower

  • Cleaning the tower surfaces, washing and cleaning the upper pan and the lower mattress of the tower

  • Cleaning the smoothness of the lower pan of the tower

  • Lubrication of fan shaft bearings according to the manufacturer's instructions

  • Lubrication of motor shaft bearings according to the manufacturer's instructions

  • Test and adjust the thrust drive (if installed)

  • Adjusting belt tension (s)

  • Control and adjust the alignment of the belts

  • Control of alignment of motor pulley shaft with impeller pulley

  • Control the couplings for tightening the screws, not playing them, etc.

  • Rotate the fan or impeller shaft by hand to ensure that the fan and bearings rotate freely

  •  Control the correct direction of rotation of the fan or impeller shaft with a blade starter

  •  Short-term fan start and control of noise and vibration

  • Drain and rinse the condenser water pipes with water and then chemicals

  • Fill the lower pan and tower and condenser pipes with water according to the manufacturer's instructions to the required amount

  •  Short-term rotation of condenser pump and fan motor according to correct installation principles

  •  Placement of fan motor amp and pump alternator in nominal plate values

  •  Test the correct distribution of water in the nozzles or upper pan, inner plates and lower pan of the cooling tower

  • Vortex flow control of the lower pan of the cooling tower

  • Test the thermostat and heater system for frost protection

  • Condenser water balance of each cell in terms of reciprocating current in multicellular systems

  • Testing the water level controls of the lower pan of the tower, including low and high limit warnings and checking the floating function

  • Control the correct installation of temperature sensors

  • Test the performance of the bypass control valve and adjust its 70-degree rotation

  • Check the correct operation of fan control relays

  • Proper VFD performance test (if installed)

  • Check the function of the vibration switch


What is the importance of setting up a cooling tower in principle?

Perhaps asking this question will help a lot in learning the above as much as possible. In answer to this question, it should be stated that the cooling tower or cooling tower is a fully advanced device consisting of electrical and mechanical components. The main components of the cooling tower should actually have its proper and optimal performance when starting up. If one of the parts does not work properly at the beginning of the commissioning process of this equipment and the refrigeration machine, its complications will soon cause damage to other parts. In fact, by correcting the errors in the installation process of the cooling tower before commissioning, irreparable damage can be prevented. In fact, the start-up operation is the last chance to fix possible errors in production or installation. Common errors such as incorrect adjustment of the cooling tower impeller angles or incorrect threading of the nozzle on the clamp will be easily noticeable at this stage.

Launching a hybrid CCTV cooling tower


The main benefits of setting up a cooling tower correctly

  • Proper operation of the cooling tower with the highest possible efficiency
  • Correct and optimal use of cold water to cool the chiller
  • Optimal operation of industrial devices connected to the cooling tower
  • Increase the life of the internal components of the device
  • No possible damage to other parts due to a defective part
  • Reduce financial losses due to possible mistakes during production
  • Reduction of casualties due to possible dangers of not operating the cooling tower properly